Compute relative humidity, dew point, absolute humidity, vapor pressure, and mixing ratio from dry‑bulb temperature, wet‑bulb temperature, or dew point. Visualize the state point on a psychrometric chart with the saturation curve.
Relative humidity (RH) is the ratio of the partial pressure of water vapor in the air to the equilibrium vapor pressure of water at the same temperature, expressed as a percentage. It is a key parameter in meteorology, HVAC design, agriculture, and materials science. The psychrometric chart graphically represents the thermodynamic properties of moist air, including dry‑bulb temperature, wet‑bulb temperature, dew point, relative humidity, and enthalpy.
RH = ( e / es ) × 100%
where e = actual vapor pressure, es = saturation vapor pressure at the dry‑bulb temperature.
The saturation vapor pressure over a flat water surface is accurately described by the Magnus formula (also known as the Magnus–Tetens approximation):
es(T) = 6.112 × exp( 17.67 × T / (T + 243.5) )
where T is in °C and es is in hPa. This equation is valid from −40°C to +50°C with excellent accuracy (±0.1 hPa) and is recommended by the World Meteorological Organization.
From the dew point temperature Td, the actual vapor pressure is simply e = es(Td). When wet‑bulb temperature Tw is known, the actual vapor pressure is obtained from the psychrometric equation:
e = es(Tw) − γ × (T − Tw) × P
where γ = 0.00066 × (1 + 0.00115 × Tw) is the psychrometric constant (in °C−1), P is the total atmospheric pressure (hPa). This formulation is widely used in engineering psychrometrics and yields results consistent with ASHRAE standards.
From e, the absolute humidity (mass of water vapor per unit volume of moist air) is:
AH = 216.7 × e / (T + 273.15) [g/m³]
and the mixing ratio (mass of water vapor per mass of dry air) is:
w = 0.622 × e / (P − e) [kg/kg]
These quantities are fundamental in atmospheric science and HVAC load calculations.
Verified against ASHRAE Fundamentals and standard psychrometric charts.
| Condition | Dry‑bulb (°C) | RH (%) | Dew Point (°C) | Absolute Humidity (g/m³) | Enthalpy (kJ/kg) |
|---|---|---|---|---|---|
| Comfortable | 25 | 50 | 14.0 | 11.5 | 50.4 |
| Dry Desert | 35 | 15 | 5.0 | 5.6 | 53.0 |
| Tropical Humid | 30 | 80 | 26.0 | 24.5 | 91.8 |
| Cold Winter | −5 | 70 | −9.5 | 2.0 | −2.1 |
| Data Center | 22 | 40 | 7.8 | 7.0 | 39.8 |
A building engineer needs to size a cooling coil for an office in Miami. Outdoor air at 35°C dry‑bulb and 70% RH (dew point 28.5°C) must be cooled to 22°C and 45% RH. Using this calculator, the engineer determines the required dehumidification: the incoming air has an absolute humidity of ~28.0 g/m³, while the target is ~8.7 g/m³. The coil must remove approximately 19.3 g of water per cubic meter of air. The enthalpy difference (≈ 95 − 42 = 53 kJ/kg) informs the cooling load. This interactive tool replaces tedious chart interpolation with instant, accurate results.
The psychrometric chart is a cornerstone of HVAC engineering. It plots dry‑bulb temperature on the x‑axis against humidity ratio or vapor pressure on the y‑axis. The saturation curve (RH = 100%) bounds the chart; below it, air is unsaturated. Iso‑RH lines curve downward from the saturation curve, representing constant relative humidity. Wet‑bulb temperature lines slope diagonally, and enthalpy lines are nearly parallel to wet‑bulb lines. Our interactive graph shows the saturation curve and selected iso‑RH lines (20%, 40%, 60%, 80%, 100%), making it easy to locate the state point and interpret its position relative to saturation.
The dew point is the temperature at which the air becomes saturated when cooled at constant pressure. On the chart, it is found by moving horizontally left from the state point to the saturation curve. This visual interpretation helps students and professionals grasp the concept intuitively.