Accurate conductor sizing based on voltage drop (NEC Annex C) and ampacity (NEC 310.15). Supports 90°C insulation optimization with 75°C terminal limits, temperature correction, and adjustment factors.
1. Load (NEC 220): I_req = Load Current × 1.25 if continuous.
2. Voltage Drop (NEC Annex C): VD = (√3 × K × I × L) / cmil (3φ) | VD = (2 × K × I × L) / cmil (1φ).
3. Ampacity (NEC 310.15): For 90°C insulation: Base_90°C × Temp_Corr × Conduit_Adj. Then limited by 75°C terminal rating (NEC 110.14(C)).
4. Final selection: Must satisfy both VD limit and ampacity after correction.
| AWG / kcmil | 60°C Cu | 75°C Cu | 90°C Cu | 75°C Al | 90°C Al |
|---|---|---|---|---|---|
| 10 AWG | 30 A | 35 A | 40 A | -- | -- |
| 8 AWG | 40 A | 50 A | 55 A | 40 A | 45 A |
| 6 AWG | 55 A | 65 A | 75 A | 50 A | 55 A |
| 4 AWG | 70 A | 85 A | 95 A | 65 A | 75 A |
| 2 AWG | 95 A | 115 A | 130 A | 90 A | 100 A |
| 1/0 AWG | 125 A | 150 A | 170 A | 120 A | 135 A |
| 4/0 AWG | 180 A | 230 A | 260 A | 180 A | 205 A |
Selecting the correct wire gauge prevents overheating, energy losses, fire hazards, and equipment malfunction. The National Electrical Code (NEC) mandates sizing conductors to handle the load current and keep voltage drop within acceptable limits (typically 3% for branch circuits, 5% total feeder+ branch). Our calculator implements both the voltage drop formula and ampacity tables to guarantee safe and efficient designs.
Voltage drop (single‑phase): VD = 2 × K × I × L / cmil
Voltage drop (three‑phase): VD = √3 × K × I × L / cmil
K = resistivity (12.9 for Cu, 21.2 for Al in Ω·cmil/ft), I = current (A), L = one‑way length (ft), cmil = conductor circular mil area.
The tool automatically picks the largest required gauge based on both voltage drop and overcurrent protection (ampacity). For copper, ampacity limits per AWG are derived from NEC Table 310.16 (75°C column). Aluminum conductors are derated accordingly (80% of copper ampacity).
A 50A solar inverter at 480V (three‑phase) located 450 feet from the main panel (copper wire, 2% max VD). Our calculator recommends 6 AWG copper (actual VD=1.93%) which also satisfies ampacity (6 AWG rating = 65A). Using undersized 8 AWG would cause 3.1% drop and increase line losses by 40% over 20 years — significant energy waste. The tool prevents such costly mistakes.
| AWG | mm² | Copper Ampacity (75°C) [A] | Circular Mils |
|---|---|---|---|
| 14 | 2.08 | 20 | 4110 |
| 12 | 3.31 | 25 | 6530 |
| 10 | 5.26 | 35 | 10380 |
| 8 | 8.37 | 50 | 16510 |
| 6 | 13.3 | 65 | 26240 |
| 4 | 21.1 | 85 | 41740 |
| 2 | 33.6 | 115 | 66360 |
| 1/0 | 53.5 | 150 | 105600 |
| 2/0 | 67.4 | 175 | 133100 |
| 3/0 | 85.0 | 200 | 167800 |
| 4/0 | 107.2 | 230 | 211600 |
According to NEC Article 210.19(A)(1) FPN No. 4, voltage drop for branch circuits should not exceed 3%, and for feeders plus branch circuits 5% maximum. Our calculator uses the 3% default but lets you adjust per design requirements. Additionally, conductor ampacity selection must consider temperature correction factors and terminal ratings — we apply conservative 75°C insulation ratings for general use.